Skip to content
FEEDER SIZING

Feeder sizing with the math shown.

Sizing a feeder is two constraints and a judgment call: the conductor has to carry the load, the voltage drop has to stay within the design criteria, and somebody has to decide what the criteria are. The arithmetic is not difficult. Doing it consistently across forty feeders on a deadline is.
Available Now

The voltage drop and conduit fill engines are live and free to use. Automated feeder extraction from drawings is in development.

The two constraints

  • Ampacity

    The conductor must carry the load current. VoltDrop compares load against the 75°C column of NEC 310.16, which is the terminal rating most equipment is listed for.

  • Voltage drop

    NEC 215.2(A)(1)(b) Informational Note recommends feeders be sized so voltage drop does not exceed 3%, with combined feeder and branch drop within 5% per 210.19(A) Informational Note No. 4.

  • Raceway

    Once conductors are selected, the raceway has to accept them. Conduit fill is checked against NEC Chapter 9 Tables 1, 4, and 5.

  • Termination temperature

    Conductor ampacity may be limited by the temperature rating of the terminations per NEC 110.14(C), independent of the conductor insulation rating.

How the calculation works

Voltage drop uses the simplified formula Vd = factor × K × I × L × PF ÷ CM, where the factor is 2 for single phase and √3 for three phase, K is the specific resistance of the conductor material corrected for operating temperature, L is one-way length in feet, and CM is circular mils from NEC Chapter 9 Table 8.

The recommended conductor is the smallest size that satisfies both ampacity and the 3% voltage drop target. Where those two constraints disagree, the calculator says which one is driving the recommendation.

  • Copper and aluminum, single and three phase
  • Temperature correction from the 75°C reference
  • Conduit type adjustment factor
  • Ampacity check against NEC 310.16
  • Voltage drop versus distance curve

Important limits

This is a planning tool. It does not perform a short-circuit or coordination study, does not apply ampacity adjustment factors for more than three current-carrying conductors in a raceway per NEC 310.15(C)(1), and does not account for continuous-load factors, derating for ambient conditions beyond the stated correction, or termination limitations specific to the equipment being served.

Results must be reviewed by a qualified professional before use on a real installation.

RELATED

Understand the job before you bid it.

VoltDrop is in early access with a limited cohort of electrical contractors. Join the Founding Contractor program and help shape what gets built next.

No card required · Limited pilot cohort